forward or reverse synchronization of the gen-set group
to the mains
synchronization between “left” and “right” buses
NOTE:
When this setpoint is set to zero, the corresponding control loop is switched
OFF.
NOTE:
See the chapter Regulation loops overview for general information about
regulation loops and their adjustment.
11.2.10.6 Setpoint: Freq int
This setpoint adjusts the relative integration factor (I-factor) of the frequency
control PI loop. The gain factor (P-factor) for the frequency loop is adjusted
by the setpoint Freq gain.
FREQ GAIN AND FREQ INT SETPOINTS ARE ACTIVE DURING:
reverse synchronization of the gen-set group back to the
mains
forward or reverse synchronization of the gen-set group
to the mains
synchronization between “left” and “right” buses
NOTE:
See the chapter Regulation loops overview for general information about
regulation loops and their adjustment.