InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
251
MGCB
forward or reverse synchronization of the gen-set group
to the mains
BTB
synchronization between “left” and “right” buses
NOTE:
When this setpoint is set to zero, the corresponding control loop is switched
OFF.
NOTE:
See the chapter Regulation loops overview for general information about
regulation loops and their adjustment.
11.2.10.6 Setpoint: Freq int
Group
Sync/Load Ctrl
Range [units]
0 .. 100 [%]
Related FW
standard v3.1.0
Description
This setpoint adjusts the relative integration factor (I-factor) of the frequency
control PI loop. The gain factor (P-factor) for the frequency loop is adjusted
by the setpoint Freq gain.
APPLICATION
FREQ GAIN AND FREQ INT SETPOINTS ARE ACTIVE DURING:
MCB
reverse synchronization of the gen-set group back to the
mains
MGCB
forward or reverse synchronization of the gen-set group
to the mains
BTB
synchronization between “left” and “right” buses
NOTE:
See the chapter Regulation loops overview for general information about
regulation loops and their adjustment.