11.2.10.9 Setpoint: Load gain
This setpoint adjusts the gain factor (P-factor) of the load control PI loop. The
integration factor (I-factor) for the load control loop is adjusted by the setpoint
Load int.
LOAD GAIN AND LOAD INT SETPOINTS ARE ACTIVE DURING:
parallel to mains operation in any mode where IM-NT
load control loop is active (see setpoint MLoad ctrl PtM),
including load ramps
BusLeft or BusRight BaseLoad control in any mode
where IM-NT load control loop is active (see setpoint
MultiLoad ctrl), including load ramps
NOTE:
When this setpoint is set to zero, the corresponding control loop is switched