InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
OFF.
NOTE:
See the chapter Regulation loops overview for general information about
regulation loops and their adjustment.
11.2.10.10 Setpoint: Load int
This setpoint adjusts the relative integration factor (I-factor) of the load
control PI loop. The gain factor (P-factor) for the load control loop is adjusted
by the setpoint Load gain.
LOAD GAIN AND LOAD INT SETPOINTS ARE ACTIVE DURING:
parallel to mains operation in any mode where IM-NT
load control loop is active (see setpoint MLoad ctrl PtM),
including load ramps
BusLeft or BusRight BaseLoad control in any mode
where IM-NT load control loop is active (see setpoint
MultiLoad ctrl), including load ramps
NOTE:
See the chapter Regulation loops overview for general information about
regulation loops and their adjustment.
11.2.10.11 Setpoint: MGCB open lev
This setpoint adjusts the end point of the bus unloading ramp, i.e. power level
at which the MGCB is opened. If this level is not reached within time period