InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
294
setpoints #Time and #Date are automatically synchronized each hour with
the controller that has lowest address. If date/time is changed at one
controller it is automatically updated also in all other controllers in the group.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.16.5 Setpoint: #Date
Group
Date/Time
Range [units]
[dd.mm.yyyy]
Related FW
standard v3.1.0
Description
The setpoint shows the date from the internal RTC clock of the controller and
can be also used to readjust it.
NOTE:
If the controller is connected to other controllers via the CAN2 bus, the
setpoints #Time and #Date are automatically synchronized each hour with
the controller that has lowest address. If date/time is changed at one
controller it is automatically updated also in all other controllers in the group.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.