InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
342
NOTE:
The counter can be readjusted/reset from InteliMonitor menu Monitor -> Set
statistics.
12.1.17.4 Value: M kVAhr I
Group
Statistics
Units
-
Related FW
standard v3.1.0
Description
This value shows the sum of kVAhr imported from the mains.
NOTE:
The counter can be readjusted/reset from InteliMonitor menu Monitor -> Set
statistics.
12.1.17.5 Value: M kVAh
Group
Statistics
Units
kVAh
Related FW
standard v3.1.0
Description
This value shows sum of kVAh that were tranferred through CB.
12.1.17.6 Value: M kWh E
Group
Statistics
Units
kWh
Related FW
standard v3.1.0
Description
This value shows the sum of kWh exported to the mains.
NOTE:
The counter can be readjusted/reset from InteliMonitor menu Monitor -> Set
statistics.