InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
402
14.2.1.22 Binary output: Syst res OK
Related FW
standard v3.1.0
Description
The output is closed while the actual reserve is above the selected reserve
for start.
14.2.1.23 Binary output: Syst res 1 OK
Related FW
standard v3.1.0
Description
The output is closed while the actual reserve is above the reserve for start
from the reserve set #1.
14.2.1.24 Binary output: Syst res 2 OK
Related FW
standard v3.1.0
Description
The output is closed while the actual reserve is above the reserve for start
from the reserve set #2.
14.2.1.25 Binary output: Syst res 3 OK
Related FW
standard v3.1.0
Description
The output is closed while the actual reserve is above the reserve for start
from the reserve set #3.
14.2.1.26 Binary output: Syst res 4 OK
Related FW
standard v3.1.0
Description
The output is closed while the actual reserve is above the reserve for start
from the reserve set #4.
14.2.1.27 Binary output: GSG params OK
Related FW
standard v3.1.0
Description
The output is closed if bus electric values are in limits and there is a sufficient
number of loaded gen-sets that do not have 2nd level alarm active (this
output is closed regardless of 1st level alarms on gen-sets). For more
information on alarm types please refer to Alarms and protections chapter.