InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
14.2.1.28 Binary output: AllAvailGS run
The output closes if all gen-sets available to take part in PMS are running
and loaded. All gen-sets having the same logical group (Control group) as
this controller has are considered + gen-sets from other logical groups if
those are currently linked with controller’s logical group (using group link
function).
14.2.1.29 Binary output: Common Wrn
The output is closed while there is at least one alarm of the Warning type
present in the alarm list. The alarm can be in any state, i.e. active
unconfirmed, active confirmed or inactive unconfirmed. See the chapter
Alarm management for more information.
14.2.1.30 Binary output: Common Fls
The output is closed while there is at least one alarm of the Sensor fail type
present in the alarm list. The alarm can be in any state, i.e. active
unconfirmed, active confirmed or inactive unconfirmed.See the chapter Alarm
management for more information.
14.2.1.31 Binary output: Common Al
The output is closed while there is at least one alarm of the Alarm only type
present in the alarm list. The alarm can be in any state, i.e. active
unconfirmed, active confirmed or inactive unconfirmed. See the chapter
Alarm management for more information.
14.2.1.32 Binary output: Common Hst
The output is closed for 1s when any alarm of History record type appears.
See the chapter Alarm management for more information.