14.2.1.33 Binary output: CommonActLev 1
Related FW
standard v3.1.0
Description
The output is closed while there is at least one 1st level (yellow) alarm
present in the alarm list. The alarm can be in any state, i.e. active
unconfirmed, active confirmed or inactive unconfirmed. See the chapter
Alarm management for more information.
14.2.1.34 Binary output: CommonAlLev 1
Related FW
standard v3.1.0
Description
This output is active if there is at least one unconfirmed 1st-level (yellow)
alarm present in the alarm list. See the chapter Alarm management for more
information.
14.2.1.35 Binary output: CommonActLev 2
Related FW
standard v3.1.0
Description
The output is closed while there is at least one 2nd level (red) alarm present
in the alarm list. The alarm can be in any state, i.e. active unconfirmed,
active confirmed or inactive unconfirmed.See the chapter Alarm management
for more information.
14.2.1.36 Binary output: CommonAlLev 2
Related FW
standard v3.1.0
Description
This output is active if there is at least one unconfirmed 2nd-level (red)
alarm present in the alarm list. See the chapter Alarm management for more
information.
14.2.1.37 Binary output: Alarm flashing
Related FW
standard v3.1.0
Description
This is the flashing alternative of the output Alarm, i.e. the output flashes with
period 1s/1s while the output Alarm is closed.
14.2.1.38 Binary output: Horn flashing