InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
405
Description
This is the flashing alternative of the output Horn, i.e. the output flashes with
period 1s/1s while the output Horn is closed.
14.2.1.39 Binary output: FltResButnEcho
Related FW
standard v3.1.0
Description
This output provides 1s pulse when:
Fault reset button is pressed on the controller front panel or
Fault reset button is pressed on any of external local/remote
terminals or
fault reset command is received via communication line or
the input FaultResButton is activated.
14.2.1.40 Binary output: HrnResButnEcho
Related FW
standard v3.1.0
Description
This output provides 1s pulse when:
Horn reset button is pressed on the controller front panel or
Horn reset button is pressed on any of external local/remote
terminals or
horn reset command is received via communication line or
the input HornResButton is activated.
14.2.1.41 Binary output: StopButnEcho
Related FW
standard v3.1.0
Description
This output provides 1s pulse when:
Stop button is pressed on the controller front panel or
Stop button is pressed on any of external local/remote terminals or
stop command is received via communication line or
the input StopButton is activated.