14.2.1.42 Binary output: StartButnEcho
Related FW
standard v3.1.0
Description
This output provides 1s pulse when:
Start button is pressed on the controller front panel or
Start button is pressed on any of external local/remote terminals or
start command is received via communication line or
the input StartButton is activated.
14.2.1.43 Binary output: MCBButnEcho
Related FW
standard v3.1.0
Description
This output provides 1s pulse when:
MCB button is pressed on the controller front panel or
MCB button is pressed on any of external local/remote terminals or
MCB close/open command is received via communication line or
the input MCBButton is activated.
14.2.1.44 Binary output: MGCBButnEcho
Related FW
standard v3.1.0
Description
This output provides 1s pulse when:
MGCB button is pressed on the controller front panel or
MGCB button is pressed on any of external local/remote terminals or
MGCB close/open command is received via communication line or
the input MGCBButton is activated.
14.2.1.45 Binary output: MODES: Off mode
Related FW
standard v3.1.0
Description
The output is closed while the controller is currently in OFF mode (either
switched by the mode selector on the front panel or by the input Remote
OFF).