InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
14.2.1.71 Binary output: ForwardSynchro
MGCB application only
The output is closed during forward synchronizing and opens when the
output MGCB status is activated (= MGCB was closed).
NOTE:
The output can be used for control of an external synchronizing module.
14.2.1.72 Binary output: MGCB status
This output indicates the MGCB position, how it is internally considered in the
controller. The position is based on MGCB feedback input and optionally also
on the MGCB fdb neg input.
If only the positive feedback input is used the output mirrors the
feedback.
If both feedbacks are used and they match each other the output
indicates the MGCB position according to the feedbacks.
If both feedbacks are used, however they do not match each other,
the output remains in previous position when they matched.
The output can be used for indication of the MGCB position.
14.2.1.73 Binary output: MCB status
This output indicates the MCB position, how it is internally considered in the
controller. The position is based on MCB feedback input and optionally also
on the MCB fdb neg input.
If only the positive feedback input is used the output mirrors the
feedback.
If both feedbacks are used and they match each other the output
indicates the MCB position according to the feedbacks.
If both feedbacks are used, however they do not match each other,
the output remains in previous position when they matched.