InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
414
controller is switched off or
controller is damaged or
incorrect/missing firmware and/or application or
corrupted setpoints
The output is intended for using in wired redundancy systems at the main
controller. Learn more about redundancy in separate chapter Redundant
controllers.
14.2.1.78 Binary output: CtrlHBeat FD
Related FW
standard v3.1.0
Description
This output is used at a redundant controller to disconnect the main
controller, connect the redundant one instead and activate it.
The output is closed:
If the input CtrlHBeat sens is configured onto any input terminal and
the redundancy controller does not sense the "heart beat" signal from
the main controller at that terminal.
If the redundant controller has not received two consequent
messages from the main controller. The address of the main
controller for the particular redundant one is selected by the the
setpoint Watched Contr
.
NOTE:
Learn more about redundancy in separate chapter Redundant controllers.
14.2.1.79 Binary output: Engines swapped
Related FW
standard v3.1.0
Description
This output is activated by the master controller for 100 ms pulse when the
priority of two gen-sets was swapped by the Running hours equalization
function.
14.2.1.80 Binary output: Logical 0
Related FW
standard v3.1.0
Description
This output is always opened. It may be used in functions (e.g. ECU outputs