or PLC modules inputs) where a binary value is required, however it has to
be continously inactive.
14.2.1.81 Binary output: Logical 1
This output is always closed. It may be used in functions (e.g. ECU outputs
or PLC modules inputs) where continuously active binary value is required.
14.2.1.82 Binary output: PeriphCommErr
The output is closed while there is an error in the communication with any
peripheral unit (e.g. IS-AIN8, IGS-PTM, ...).
14.2.1.83 Binary output: WrongPhSeq
Binary output WrongPhSeq is active when at least one of the following
conditions is fulfilled: Mains/Bus phase is inverted or wrong mains/bus phase
sequence or opposed mains/bus phase sequence is detected.
14.2.1.84 Binary output: User Button 1
This output can be specified for example on buttons on IV-5/8 or in SCADA
diagram in InteliMonitor. Its state depends on function assigned to the related
button.
It is possible to lock UserButton commands in configuration to specific user
level. Buttons 1-8 and 9-16 are locked separately.
Pressing the button changes the state of log. binary output
User Button X to closed. When the output is closed and the
button is pressed state is not changed.
Pressing the button changes the state of log. binary output
User Button X to opened. When the output is opened and
the button is pressed state is not changed.