InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
62
ISLAND
ENABLE
PARALLEL
ENABLE
SYNCHRO
ENABLE
MFSTART
MGCBPARALCLOSE
SHORT DESCRIPTION
YES
YES
NONE
NO
YES
- Island and Parallel operations are possible.
- Transfer with synchronization via InteliMains is
not available
- Gen-sets will not be started when the Mains
fails.
- Gen-sets will synchronize directly to the Mains
(MGCB already closed) , i.e. synchronization
transfer from Island to Parallel
YES
YES
NONE
YES
MCB CLOSED
- Island and Parallel operations are possible.
- Transfer with synchronization via InteliMains is
not available
- Gen-sets will be started when the Mains fails.
- Gen-sets will synchronize directly to the Mains
(MGCB already closed) , i.e. synchronization
transfer from Island to Parallel
- MGCB will be closed if the MCB is closed
YES
YES
NONE
NO
MCB CLOSED
- Island and Parallel operations are possible.
- Transfer with synchronization via InteliMains is
not available
- Gen-sets will not be started when the Mains
fails.
- Gen-sets will synchronize directly to the Mains
(MGCB already closed) , i.e. synchronization
transfer from Island to Parallel
- MGCB will be closed if the MCB is closed
YES
YES
REVERSE
YES
YES
- Island and Parallel operations are possible.
- Transfer with synchronization from Island to
Parallel is enabled
- Gen-sets will be started when the Mains fails.
- Gen-sets will synchronize directly to the Mains
(MGCB already closed), i.e. synchronization
transfer from Mains to Parallel
YES
YES
REVERSE
YES
NO
- Island and Parallel operations are possible.
- Transfer with synchronization from Island to
Parallel is enabled (Mains to Parallel N/A)
- Gen-sets will be started when the Mains fails.
YES
YES
REVERSE
NO
YES
- Island and Parallel operations are possible.
- Transfer with synchronization from Island to
Parallel is enabled
- Gen-sets will not be started when the Mains
fails.
- Gen-sets will synchronize directly to the Mains
(MGCB already closed), i.e. synchronization
transfer from Mains to Parallel
YES
YES
REVERSE
NO
NO
- Island and Parallel operations are possible.
- Transfer with synchronization from Island to
Parallel is enabled (Mains to Parallel N/A)
- Gen-sets will not be started when the Mains
fails.