InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
63
ISLAND
ENABLE
PARALLEL
ENABLE
SYNCHRO
ENABLE
MFSTART
MGCBPARALCLOSE
SHORT DESCRIPTION
YES
YES
REVERSE
YES
MCB CLOSED
- Island and Parallel operations are possible.
- Transfer with synchronization from Island to
Parallel is enabled
- Gen-sets will be started when the Mains fails.
- Gen-sets will synchronize directly to the Mains
(MGCB already closed), i.e. synchronization
transfer from Mains to Parallel
- MGCB will be closed if the MCB is closed
YES
YES
REVERSE
NO
MCB CLOSED
- Island and Parallel operations are possible.
- Transfer with synchronization from Island to
Parallel is enabled
- Gen-sets will not be started when the Mains
fails.
- Gen-sets will synchronize directly to the Mains
(MGCB already closed), i.e. synchronization
transfer from Mains to Parallel
- MGCB will be closed if the MCB is closed
YES
NO
NONE
YES
NO
- Island operation is possible.
- Transfer with synchronization is N/A
- Gen-sets will be started when the Mains fails.
YES
NO
NONE
NO
NO
- Island operation is possible.
- Transfer with synchronization is N/A
- Gen-sets will not be started when the Mains
fails.
YES
NO
NONE
YES
MCB CLOSED
- Island operation is possible.
- Transfer with synchronization is N/A
- Gen-sets will be started when the Mains fails.
- MGCB will be closed if the MCB is closed
YES
NO
NONE
NO
MCB CLOSED
- Island operation is possible.
- Transfer with synchronization is N/A
- Gen-sets will not be started when the Mains
fails.
- MGCB will be closed if the MCB is closed
NO
YES
FORWARD
NO
NO
- Parallel operation is possible.
- Transfer with synchronization from Mains to
Parallel is enabled
- Gen-sets will not be started when the Mains
fails.
- Gen-sets will first synchronize on the bus before
synchronizing via MGCB
NO
YES
NONE
NO
YES
- Parallel operation is possible.
- Transfer with synchronization via InteliMains is
N/A
- Gen-sets will not be started when the Mains
fails.
- Gen-sets will synchronize directly to the Mains
(MGCB already closed), i.e. synchronization
transfer from Mains to Parallel