Finally, we get the run time of gen-set 3 before next swapping:
SwapTimeG2 = 11 0 + 10 + 1 = 22
Please refer to figure below to understand the evolution of RHE of gen-sets in this particular case.
0
10
20
30
40
50
60
70
80
90
RHE
Step
1 2 3 4 5 6 7 8 9 10 11 12 13
Figure: Running Hours Equalization example, 3 gen-sets with same initial RHE
step
0
1
2
3
4
5
6
7
8
9
10
11
12
13
RHE1
0
11
11
11
11
33
33
33
33
55
55
55
55
77
RHE2
0
0
11
11
22
22
33
33
44
44
55
55
66
66
RHE3
0
0
0
22
22
22
22
44
44
44
44
66
66
66
Run G1 (Δ RHE1)
0
11
0
0
0
22
0
0
0
22
0
0
0
22
Run G2 (Δ RHE2)
0
0
11
0
11
0
11
0
11
0
11
0
11
0
Run G3 (Δ RHE3)
0
0
0
22
0
0
0
22
0
0
0
22
0
0