Servicing
Servicing
Degassing the Dispenser
When replacing or servicing dispenser hydraulics the dispensers must be de-gassed.
Degas the Dispenser
- Isolate the dispenser by closing the inlet gas supply valves at the base of the
unit or at the priority panel.
- Fill one or more CNG bottles until the dispenser pipework is completely
depressurized. Ensure that the isolation valve remains open during this
process.
Open the bleed valve on the utility manifold (where fitted) to remove any remaining gas
inside the dispenser.