35Operating the control software
– Band Channel 2: with this setting you set the proportional range for the
internal P/PI supply air controller in %rh.
Note: this setting appears only if "Control Mode CH 2/4" is set to "RH P"
or "RH PI" and "Control Channels" is set to "Dual".
Factory setting: 15 %
Setting range: 6 ... 65 %
– Damp Channel 2: with this setting you set the time in seconds after which
the supply air controller takes over the control of the demand signal.
Note: this setting appears only if "Control Mode CH 2/4" is set to "RH P"
or "RH PI" and "Control Channels" is set to "Dual".
Factory setting: 5 seconds
Setting range: 1 ... 60 seconds