4. Heating voltage/control voltage
Heating voltage
The Condair Mk5 steam humidiers are available with various heating voltages.The maximum
achievable steam capacity and the power consumption are directly dependent on the selected
heatingvoltage(seetable).
400 V/3~
220 V/3~
415 V/3~ 240 V/1N~ 230 V/1N~ 200 V/3~
50...60 Hz 50...60 Hz 50...60 Hz 50...60 Hz 50...60 Hz 50...60 Hz
Condair Mk5
Visual.../Process...
kg/h kW A kg/h kW A kg/h kW A kg/h kW A kg/h kW A kg/h kW A
...5-..
5.0 3.8 5.5 4.6 3.4 9.0 5.1 4.0 6.0 5.1 4.0 17.0 5.1 4.0 16.5 3.9 3.0 8.2
...8-..
8.0 6.0 8.7 7.3 5.5 14.4 8.4 6.5 9.0 8.7 6.5 27.2 8.0 6.0 26.0 5.8 4.5 13.1
...10-..
10.0 7.5 11.0 9.0 6.7 17.7 10.3 8.0 11.5 10.3 8.0 33.0 10.0 7.4 32.0 7.1 5.5 16.1
...16-..
16.0 12.0 17.4 14.6 10.9 28.7 16.7 13.0 18.1 –– –– –– –– –– –– 11.6 9.0 26.1
...20-..
20.0 14.9 21.5 18.0 13.5 35.4 20.6 16.0 22.3 –– –– –– –– –– –– 14.3 11.1 32.2
...24-..
24.0 18.1 26.2 21.9 16.4 43.1 25.1 19.5 27.2 –– –– –– –– –– –– 17.4 13.5 39.2
...30-..
30.0 22.3 32.3 27.0 20.2 53.1 30.6 24.0 33.5 –– –– –– –– –– –– 21.5 16.7 48.3
...40-..
40.0 30.0 43.3 36.2 27.2 71.4 41.5 32.3 45.0 –– –– –– –– –– –– 28.8 22.4 64.9
...50-..
A 20.0
+
30.0
14.9
+
22.3
21.5
+
32.3
18.0
+
27.0
13.5
+
20.2
35.4
+
53.1
20.6
+
30.6
16.0
+
24.0
22.3
+
33.5
–– –– –– –– –– ––
14.3
+
21.5
11.1
+
16.7
32.2
+
48.3
B
...60-..
A 30.0
+
30.0
22.3
+
22.3
32.3
+
32.3
27.0
+
27.0
20.2
+
20.2
53.1
+
53.1
30.6
+
30.6
24.0
+
24.0
33.5
+
33.5
–– –– –– –– –– ––
21.5
+
21.5
16.7
+
16.7
48.3
+
48.3
B
...80-..
A 40.0
+
40.0
30.0
+
30.0
43.3
+
43.3
36.2
+
36.2
27.2
+
27.2
71.4
+
71.4
41.5
+
41.5
32.3
+
32.3
45.0
+
45.0
–– –– –– –– –– ––
28.8
+
28.8
22.4
+
22.4
64.9
+
64.9
B
Shouldyourequireaunitwithadifferentheatingvoltage,pleasecontactyoursupplier.
Control voltage
CondairMk5steamhumidiersaredesignedforastandardcontrolvoltageof220...240V/50...60Hz.
Ifusedinsystemswithoutseparatecontrolvoltagesupply,theCondairMk5maybeequippedwith
an optional transformer 400-500 V/230V(seechapter4.4).
Mk5 Visual VE 24-400V/3~