43
Remote operating and fault indication
Ifyoursteamhumidierisequippedwiththeoptionalremoteoperatingandfaultindication(option“RFS”),
theoperatingstatuswillbeshownasfollows:
Display on unit Meaning Activated remote display relay
Green LED lit
Steam production
K1 “Steam production”
Red LED lit
Insoluble problem
K2 “Error”
RedLEDashing Fault elimination No message
Yellow LED ashing
Steam cylinder service due
K3 “Maintenance”
Unit switched on
Unitreadyforoperation
K4 “Unit on”
6.3 Taking out of operation
Thefollowing procedure is followed when it isrequiredtoshut down the steam humidier, e.g. for
maintenancework:
• Closetheltervalve/shut-offvalveinthewaterfeedline.
• Brieydepressthedrainswitchformorethan7seconds.Theheatingvoltageisisolatedandthe
steam cylinder empties.
• Waituntilthesteamcylinderisempty(approx.5-10minutes),thenoperatetheoff-switchonthe
steamhumidier.
• Isolatethesteamhumidierfromthemainssupply:Switchoffallserviceswitchesinthemainssup-
plylines(heatingandcontrolvoltage)andsecurethemintheoffposition.