5.5.3 Notes on component installation
Important note:
All connecting cables in the electrical installation are to be fed in via the cable glands on the base
oftheunit(theexceptiontothisistheheatingvoltageconnectioncable,forwhichthespecialclamp
isprovided).
– Thedetailsrelatingtoindividualcomponentsaretobenotedandfollowed.
Heating voltage supply Up
Caution!Beforeconnecting,ensurethatthemainsvoltagecorrespondswiththeheating volt-
age for the unit (see mains code on the type label).
Thehumidier(inthecaseoftwinnedunits,eachseparateunit)istobeconnectedtothemainssupply
inaccordancewiththeconnectionschematic,viaaservice switch “Q3” (an all pole disconnecting
devicewithaminimumcontactopeningof3mmisanessentialrequirement)andan“F3” fuse group
(essentialrequirement:fusesaretobeasdetailedinthefollowingtable).Thesupplywiringistobefed
intotheunitviathetension-relievingdevice(cableclamp)andconnectedtotheterminalsofthe“K1”
mains contactor.
Caution! Onequipmentversionscombiningtwobasicunits,eachunithasatypelabel. .
LC display
400 V/3~
50…60 Hz
220 V/3~
50…60 Hz
415 V/3P~
50…60 Hz
240 V/1N~
50…60 Hz
230 V/1N~
50…60 Hz
200 V/3~
50…60 Hz
P
N
max. in kW
I
N
max. in A
A
L
min. in mm
2
F3 in A, quick acting
P
N
max. in kW
I
N
max. in A
A
L
min. in mm
2
F3 in A, quick acting
P
N
max. in kW
I
N
max. in A
A
L
min. in mm
2
F3 in A, quick acting
P
N
max. in kW
I
N
max. in A
A
L
min. in mm
2
F3 in A, quick acting
P
N
max. in kW
I
N
max. in A
A
L
min. in mm
2
F3 in A, quick acting
P
N
max. in kW
I
N
max. in A
A
L
min. in mm
2
F3 in A, quick acting
Mk5 Visual 5-..
Mk5 Process 5-..
3,8 5,5 1,5 10 3,4 9,0 2,5 16 4,0 6,0 1,5 10 4,0 17,0 2,5 20 4,0 16,5 4,0 20 3,0 8,2 1,5 10
Mk5 Visual 8-..
Mk5 Process 8-..
6,0 8,7 1,5 10 5,5 14,4 2,5 16 6,5 9,0 1,5 10 6,5 27,2 6,0 32 6,0 26,0 6,0 32 4,5 13,1 1,5 16
Mk5 Visual 10-..
Mk5 Process 10-..
7,5 11,0 1,5 16 6,7 17,7 2,5 20 8,0 11,5 1,5 16 8,0 33,0 10,0 40 7,4 32,0 10,0 40 5,5 16,1 2,5 20
Mk5 Visual 16-..
Mk5 Process 16-..
12,0 17,4 2,5 20 10,9 28,7 6,0 32 13,0 18,1 2,5 20 ––– ––– ––– ––– ––– ––– ––– ––– 9,0 26,1 6,0 32
Mk5 Visual 20-..
Mk5 Process 20-..
14,9 21,5 6,0 25 13,5 35,4 10,0 40 16,0 22,3 4,0 25 ––– ––– ––– ––– ––– ––– ––– ––– 11,1 32,2 10,0 40
Mk5 Visual 24-..
Mk5 Process 24-..
18,1 26,2 6,0 32 16,4 43,1 16,0 63 19,5 27,2 6,0 32
––– ––– ––– ––– ––– ––– ––– ––– 13,5 39,2 16,0 63
Mk5 Visual 30-..
Mk5 Process 30-..
22,3 32,3 10,0 40 20,2 53,1 16,0 63 24,0 33,5 10,0 40 ––– ––– ––– ––– ––– ––– ––– ––– 16,7 48,3 16,0 63
Mk5 Visual 40-..
Mk5 Process 40-..
30,0 43,3 16,0 63 27,2 71,4 25,0 80 32,3 45,0 16,0 63 ––– ––– ––– ––– ––– ––– ––– ––– 22,4 64,9 25,0 80
Mk5 Visual 50-..
Mk5 Process 50-..
A
14,9
+
22,3
21,5
+
32,3
6,0
+
10,0
25,0
+
40,0
13,5
+
20,2
35,4
+
53,1
10,0
+
16,0
40
+
63
16,0
+
24,0
22,3
+
33,5
4,0
+
10,0
25
+
40
––– ––– ––– ––– ––– ––– ––– –––
11,1
+
16,7
32,2
+
48,3
10,0
+
16,0
40
+
63
B
Mk5 Visual 60-..
Mk5 Process 60-..
A
22,3
+
22,3
32,3
+
32,3
10,0
+
10,0
40,0
+
40,0
20,2
+
20,2
53,1
+
53,1
16,0
+
16,0
63
+
63
24,0
+
24,0
33,5
+
33,5
10,0
+
10,0
40
+
40
––– ––– ––– ––– ––– ––– ––– –––
16,7
+
16,7
48,3
+
48,3
16,0
+
16,0
63
+
63
B
Mk5 Visual 80-..
Mk5 Process 80-..
A
30,0
+
30,0
43,3
+
43,3
16,0
+
16,0
63,0
+
63,0
27,2
+
27,2
71,4
+
71,4
25,0
+
25,0
80
+
80
32,3
+
32,3
45,0
+
45,0
16,0
+
16,0
63
+
63
–––
––– ––– ––– ––– ––– ––– –––
22,4
+
22,4
64,9
+
64,9
25,0
+
25,0
80
+
80
B
AB