EasyManua.ls Logo

Condair Mk5 - Page 37

Condair Mk5
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
37
Control voltage supply Uc
Caution!Beforeconnecting,makesurethatthemainsvoltagecorrespondswiththecontrol
voltage of the unit (200…240 V, 50…60 Hz).
Caution!Thehumidiermustonlybeconnectedtoamains supply with a protective con-
ductor.
TheconnectiontothecontrolvoltageUcismadeinaccordancewiththeconnectionschematic,tothe
terminal “X1” on the supply module. The customer is to install a service switch Q4 in the supply line
(allpoledisconnectingdevicewithaminimumcontactopeningof3mm)andanF4 fuse (max. 10 A
slow acting) (thesearebothessentialrequirements).
Note:Onversionsinwhichtwounitsareincorporated,thecontrolvoltageconnectionismadetothe
unitttedwiththedisplayandoperatingfacility(unitA).Theterminal“X1”ofthesecondunit(unitB)
remains unused. To supply the control voltage to unit B, the terminals “X6” on the supply modules of
both units must be connected using the supplied cable.
Thecross-sectionofthemainscablemustcomplywiththeapplicablelocalregulations(minimumof
1.5 mm
2
).
External safety circuit
Toensurethesafetyofthehumidiersystem,itisessentialthataso-calledexternalsafetycircuitbe
provided to monitor the operation.
To this end, the potential-free contacts (max. contact loading 250V/5A) oftheexternalmonitoring
devices(e.g.maximumhumidistat,owmonitor,ventilationinterlock,etc.)areconnectedin series with
the corresponding contacts on the terminal “X1”,inaccordancewiththeconnectionschematic.
Caution, danger of electric shock! The mains voltage is connected to terminal “X1” (up to
240V).Thesteamhumidiermustthereforebeisolatedfromthemainssupply(powerandcontrol
components),beforestartingtheconnectionwork.
If,forwhateverreason,noexternalmonitoringdevicesareconnected,aconnectingbridge“J”mustbe
installed on the appropriate contacts on the terminal strip “X1”.
Do not apply any extraneous voltage to the terminals.
Thecross-sectionofthecablemustcomplywiththeapplicablelocalregulations(minimumof1mm
2
).
Remote operating and fault indication H1 (Option “RFS”)
TheoptionalremoteoperatingandfaultindicationPCBistobeconnectedviatheconnectionsocket
“J3”onthecontrolboard.TheremoteoperatingandfaultindicationPCBcontainsthepotential-free
relaycontactsK1…K4fortheconnectionofthefollowingoperatingandfaultindications:
K1 “Steam production”: This relay closes as soon as the unit produces steam.
K2 “Fault”: This relay is activated if there is a fault.
K3“Maintenance”: Thisrelayisactivatedwhenthesetserviceintervalhasexpired.
K4“UnitOn”: Thisrelayclosesassoonastheunitisswitchedonviathemainswitch.
The maximum contact loading is 250V/5A.
Appropriatesuppressormodulesaretobeusedfortheswitchingofrelaysandminiaturecontactors.

Table of Contents

Related product manuals