Water supply
Thewaterfeedpipe(min.internalØ:8mm)istobeconnectedviathelter valve that is available as
anaccessory,totheconnectionontheunit(seedetailedillustration).Alternatively,ashut-off valve and
a water lter maybeinstalled.Theinstallationoftheltervalveshouldbemadeascloseaspossible
tothesteamhumidier.
Warning - danger of damage! Union nutatthehumidierconnectionmustbehand-tightened
only.
Thefollowingconnectionspecicationsmustbeobserved:
– Connectiononunit:G 1/2" (Union nut)
– Min. inner Ø of supply line: 8 mm
– Admissible mains pressure 1.0 to 10.0 bar(hammer-freesystem)
For mains pressures >10 bar, connection must be made via pressure reducing valve (adjusted to
2.0bar).Formainspressures<1.0barpleasecontactyoursupplier.
– Supply rate: 1 l/min per 15 kg/h steam capacity
– Admissible supply temperature: 1…40 °C
– Notes on water quality:
– ForthewatersupplyoftheCondairMk5,useexclusivelyuntreated drinking water or fully
demineralized water.
Note:Theuseoffullydemineralizedwaterreducesthetimeformaintenanceandcleaningtoa
minimum.
– The use of additives such as corrosion inhibitors, disinfectants, etc. is not allowed, since these
additives may endanger health and affect proper operation.
– IftheCondairMk5shallbeoperatedwithsoftenedorpartlysoftenedwater,pleasecontactyour
supplier.
– The connection material must be pressure-proof andcertiedforuseindrinking water supply
systems.
Caution! Fullydemineralizedwaterisaggressive.Whenmakingconnectionstoafullydem-
ineralizedwatersystem,useexclusivelyplasticorstainlesssteelinstallationmaterials(min.
DIN1.4301).
– Important! Beforeconnectingthewaterlinetotheunit,thelinemustbeushedthoroughly.
Water drain
Thewaterdrainageiseffectedwithoutpressure.Thus,inordertoavoidanydammingofthewater,the
drain pipe must be led straight down into a drainage funnel, through a piece of hose with a min.
length of 30 cm. Subsequently, the drain pipe is connected via siphontothewastewatersystemof
thebuilding.Theminimuminsidediameterof40mmmustbeobservedoverthewholelengthofthe
drainpipe.Makecertainthatthedrainpipeiscorrectlyxedandeasilyaccessibleforinspectionsand
cleaning purposes.
Thefollowingconnectionspecicationsmustbeobserved:
– Drainage capacity: approx. 2,5l/min per 15 kg/h steam capacity
– Drainage temperature: 60…90 °C
Warning! Use only temperature-resistant installation materials!
Warning! Fully demineralized water is aggressive. Theconnectionsforademineralized
watersystemshouldbemadeexclusivelyfrom stainless steel (min. DIN 1.4301) or chemi-
cally resistant plastics (e.g. polypropylene).
– Connectiononunit:hose connection Ø40 mm
Warning!Hosemustbesecuredtotheunitconnectionwithahoseclamp.
– Min. inner Ø of drain line: 40 mm
– Min.downslopeaftersiphon:10 %