16 Operation
4.3 Commissioning after an interruption of operation
The following description outlines the start up procedure after an interruption of operation (e.g. after
servicing the steam humidier). It is assumed that rst-time commissioning has been carried out prop-
erly by the service technician of your Condair representative and the Condair RM has been congured
accordingly.
1. When putting the steam humidier into operation after work has been carried out on the steam sys-
tem, the operating personnel must check whether the steam pipe is open over the entire length.
WARNING!
Danger of scalding!
Asteamlinethatisreducedincrosssectionorcompletelyclosedwillcauseanexcessive
increase in pressure in the steam tank when the unit is operating and could lead to the risk
of scalding accidents!
2. Examine the steam humidier and installation for possible damage.
DANGER!
A damaged unit or systems with damaged installations may present danger to human life
or cause severe damage to material assets.
Therefore: Damaged systems and/or systems with damaged or faulty installations must not be
operated.
3. Relocate the unit cover and lock it with the retaining screw.
4. Open the lter valve / shut-off valve in the water supply line.
5. Switch on the electrical isolator in the mains supply line.
6. Switch on the unit switch of the steam humidier.
The Condair RM carries out an automatic system test (initialising). If a malfunction is detected during
the system test, the status LED indicates a "Warning" (LED lights yellow) or "Fault" (LED lights red).
If the is successful, the steam tank lls up and a function check on the level unit is carried out.
Note: If a malfunction is detected during the function check on the level unit, the status LED indicates
a "Warning" (LED light yellow) or "Fault" (LED light red).
If the function check on the level unit is successful, the Condair RM will be in normal operating
mode and the LED blinks green. As soon as a steam demand is present or the humidifying opera-
tion is started manually, the heating current is switched on, the status LED lights green and steam
is produced after a short time.