53Maintenance
7.8 Resetting the maintenance counter
If the maintenance work (unit maintenance or replacement of the optional lter cartridge) has been car-
ried out, the maintenance indication or maintenance counter must be reset. Proceed as follows:
1. Make sure that the unit cover is attached and secured.
2. Switch on the Condair RM.
3. Press the menu button to access the main menu and enter the password "0000" (if the display lock
is activated).
4. Select the "Service" submenu and enter the password "3562".
5. Resettingthemaintenancecounterforthe"unitmaintenance":
Important:themaintenancecounterforthe"unitmaintenance"mustberesetonly,ifallwork
of the unit maintenance has been carried out!
• Select "Device Service" submenu.
• Select the reset function "Service Done".
Resettingthemaintenancecounterforthe"cartridgereplacement":
Important:themaintenancecounterforthe"cartridgereplacement"mustberesetonly,ifthe
cartridge has been replaced!
• Select "Filter Cartridge" submenu.
• Select the reset function "Cartridge Replaced".
4. The reset dialogue appears:
• Press the <Tick> button to reset the corresponding maintenance counter. The maintenance
indication and the maintenance counter are reset.
• Press the <Cancel> button if the unit maintenance work or the replacement of the lter cartridge
has not been completed yet and you want abort the reset procedure. The control unit returns to
the "Service" submenu.