28 Conguration of Condair RM control software
6.2 Settingsinthe"Service"menu
Accessingthe"Service"menu
• Press the <Menu> button on the top right corner of the display. Then, enter the password "0000" (if
main menu is congured with password protection). The main menu appears.
Note: The password for the user menu can be modied in the "Engineering > Administration >
Password" submenu.
• Select menu item "Service" in the main menu.
• Enter the password ("3562") in the password entry window that appears and conrm. Then, the
"Service" menu appears.
Note: The content of the "Service" menu depends on the selected HVAC application. The following
description of the settings lists all available parameters of the "Service" menu.
SettingparametersMenu"Service"
Error List Shows the list with the current warning and error messages.
ErrorHistory Shows a list of the last 50 warning and error messages.
Steam Generator
Error List Shows the list with the current warning and error messages of the Condair RM steam humidier
ErrorHistory Shows a list of the last 50 warning and error messages of the Condair RM steam humidier
Water Supply Water supply settings for the Condair RM.
– Type: Determining the water supply type
– Tap Water
– RO (Reverse Osmosis Water)
– Filter Cartridge
– Carbonate hardness: Setting the carbonate hardness of the supply water in °dH.
Note: This menu item appears only if the supply water type is set to "Tap Water" or "Filter
Cartridge".
Device Service
View and reset the service values of the Condair RM.
– Service Done: Resetting the maintenance counter after maintenance has been carried out.
– Heat Count: Shows the operating hours extrapolated to 100% steam output
– Next Service: Remaining time in hours until the next maintenance is due.
Filter Cartridge Display, set and reset of the lter cartridge service values.
– Cartridge Size: Determining the size of the lter cartridge used.
– Small
– Large
– Cartridge Replaced: Resetting the maintenance counter after replacing the lter cartridge.
– Water Count: Shows the water consumption in liters.
– Replace in: Remaining water consumption in liters until the next replacement of the lter
cartridge is due.
Hardware Hardware information of the heating channels.
– Hardware:
– Sw. Cycles 1: Number of switching cycles of heating channel No. 1
– Sw. Cycles 2: Number of switching cycles of heating channel No. 2
– Sw. Cycles 3 to Sw. Cycles 5: Not used with Condair RM
– Replace HW 1: Theoretical remaining switching cycles of heating channel No. 1
– Replace HW 2: Theoretical remaining switching cycles of heating channel No. 2
– Replace HW 3 to Replace HW 5: Not used with Condair RM
– Op. Hours HW 1: Current operating hours of the heating channel No. 1
– Op. Hours HW 2: Current operating hours of the heating channel No. 2
– Op. Hours HW 3 to Op. Hours HW 5: Not used with Condair RM
Draining Draining the steam tank.
Device test
– Level Test: Performing a functional test of the level unit.
Restart Restart device software