34 Maintenance
7.2 Maintenance intervals
To maintain operational safety the Condair RM steam humidier must be maintained at regular intervals.
The control software of the Condair RM features a maintenance counter for the unit maintenance of the
steam humidier and one for the Replacement of the lter cartridge (only active if system is congured
for the operation with the optional lter cartridge). The maintenance counters for the unit maintenance
or the replacement of the lter cartridge, respectively are determined at the initial commissioning based
on the carbonate hardness of the supply water.
Maintenanceintervalsinhoursfor"unitmaintenance"
The following table gives you an overview of the approximate interval times for the unit maintenance at
100 % steam output based on the carbonate hardness of the supply water and the unit size. When using
RO water the maintenance interval time for the unit maintenance is set xed to 2000 hours.
Maintenanceintervaltimes"unitmaintenance"inhours
Supply water type Carbonatehardness[°dH]
supply water
Condair RM
2 4 6 8
Tap water 1 2800 1400 1050 700
2 2520 1260 945 630
3 2280 1140 855 570
4 2040 1020 765 510
5 1840 920 690 460
6 1640 820 615 410
7 1480 740 555 370
8 1320 660 495 330
9 1160 580 435 290
10 1040 520 390 260
11 920 460 345 230
12 800 400 300 200
13 720 360 270 180
14 640 320 240 160
15 560 280 210 140
16 480 240 180 120
17 440 220 165 110
18 400 200 150 100
19 360 180 135 90
20 320 160 120 80
21 280 140 105 70
22 240 120 90 60
23 200 100 75 50
24 160 80 60 40
25 120 60 45 30
>25
120 60 45 30
RO water not congurable 2000
Important! Independently whether the Condair RM is operated with tap water, RO water or lter cartridge
water the unit maintenance is to be carried out at least once a year.