25Conguration of Condair RM control software
Congurationprocedureforhumiditycontrolviaanexternalhumiditycontroller:
1. Reset RM Control to factory settings.
(Path: Engineering > Omega Control Board > Factory Reset)
2. Reset Condair RM Display to factory settings.
(Path: Engineering > Admin > Display > Factory Reset)
3. Set "System Mode" to "Steam Generator":
(Path: Engineering > Omega Control Board > System Mode > Steam Generator)
4. Set steam humidier "Control Mode" to "Demand":
(Path: Engineering > Steam Generator > Steaming Settings > Control Mode > Demand)
5. Determine the demand signal setting:
(Pfad: Engineering > Steam Generator > Steaming Settings > Cntrl. Input Signal)
• Determine the demand signal type ("0 - 5V", "1 - 5V", "0 - 10V", "2 - 10V", "0 - 20V", "0 - 16V",
"3 - 16V", "0 - 20mA", "4 - 20mA" or "On/Off")
6. Determine unit size.
(Path: Engineering > Steam humidier > Tank Settings > Capacity)
Note: The unit size can be found on the rating plate of the Condair RM under steam output.
7. Determine supply water type and cartridge size:
• Determine the supply water type ("Tap Water", "RO" or "Filter Cartridge") and the carbonate
hardness of the supply water (only if water supply type is set to " Tap Water" or "Filter Cartridge")
(Path: Service > Steam humidier > Water Supply > Type)
• Determine cartridge size (only if water supply type is set to "Filter Cartridge")
(Path: Service > Steam Generator > Filter Cartridge > Cartridge Size)
8. Set current date and time of day:
(Path: User > General)
• Set date
• Set time of day