57Fault elimination
Warning Fault Message Possible causes Remedy
––– E46
Max.draintime Maximum drain time of the Condair RM exceeded.
Note: The operation of the Condair RM is stopped. After the fault
has been eliminated, the Condair RM must be switched off and on
again.
Drain pump not or not correctly
connected.
Check/correctly connect drain
pump.
Drain hose inside the unit kinked
or blocked.
Check/clean drain hose inside the
unit, replace if necessary.
Water drain obstructed (external
drain line or funnel blocked).
Clean external drain line and si-
phon.
Hoses to level unit blocked. Clean or replace hoses.
Drain pump defective. Replace drain pump.
––– E47 Level unit The level in the steam tank of the Condair RM is in an unaccept-
able range.
Note: The operation of the Condair RM is stopped. After the fault
has been eliminated, the Condair RM must be switched off and on
again.
Level unit defective. Replace level unit.
––– E56 Int. safety loop The internal safety loop of the Condair RM is open.
Note: The operation of the Condair RM is stopped. After the fault
has been eliminated, the Condair RM must be switched off and on
again.
Overtemperature switch(es) not
connected correctly.
Let have the wiring of the overtem-
perature switch(es) checked/cor-
rectly connected by an electrician.
Overtemperature switch(es) de-
fective
Let have the overtemperature
switch(es) be replaced by an
electrician.
Overtemperature switch(es) has/
have triggered.
Let have the Condair RM be
checked by a Condair service
technician.
Important: for safety reasons
all heating elements have to be
replaced if the over temperature
switch(es) has/have triggered.
––– E87
Local24Vsupply Local 24 V voltage on the control board the Condair RM out of
valid range.
Note: The Condair RM goes into standby mode. If the fault disap-
pears on its own, the Condair RM continues to run normally.
Short circuit on the supply mod-
ule or supply module defective.
Contact your Condair represen-
tative.
––– E88
Local5Vsupply Local 5 V voltage on the control board of the Condair RM out of
valid range.
Note: The Condair RM goes into standby mode. If the fault disap-
pears on its own, the Condair RM continues to run normally.
Short circuit on the supply mod-
ule or supply module defective.
Contact your Condair represen-
tative.