33Mounting and installation work
Abb. 12: Steam line with solid piping and insulation
The following notes should be observed:
The minimum internal diameter of the steam line (diameter dependent on the steam generator)
should be applied over the entire length of the piping.
Use exclusively stainless steel (recommended, min. DIN 1.4301) or copper pipe.
To minimize the condensate formation (=loss), the steam pipes must be insulated.
Ømin.
200 mm
min. 15 %
+
min. 15 %
min. 15 %
min. 15 %
Ømin.
200 mm
Rmin.: 5 x D
min. 1000 mm
max. 4 m
max. 4 m