33Mounting and installation work
Abb. 12: Steam line with solid piping and insulation
The following notes should be observed:
– The minimum internal diameter of the steam line (diameter dependent on the steam generator)
should be applied over the entire length of the piping.
– Use exclusively stainless steel (recommended, min. DIN 1.4301) or copper pipe.
– To minimize the condensate formation (=loss), the steam pipes must be insulated.
Ømin.
200 mm
min. 15 %
+
min. 15 %
–
min. 15 %
–
min. 15 %
–
Ømin.
200 mm
Rmin.: 5 x D
min. 1000 mm
max. 4 m
max. 4 m