Table 5 TROUBLESHOOTING CHART, continued
PROGRAMMER LCD DISPLAY
CODE
EFFECT OF FAULT
POSSIBLE CAUSE
SET/CLEAR CONDITIONS
8 — DIAGNOSTICS & TROUBLESHOOTING
49 Parameter Change Fault 1. This is a safety fault caused by a Set: Adjustment of a parameter setting
ShutdownMotor;
change in certain parameter that requires cycling of KSI.
ShutdownMainContactor; settings so that the vehicle will not
Clear: Cycle KSI.
ShutdownEMBrake;
operate until KSI is cycled.
ShutdownThrottle;
For example, if a user changes the
FullBrake;
Throttle Type this fault will appear
ShutdownPump.
and require cycling KSI before the
vehicle can operate.
5167 OEM Faults 1. These faults can be defined by the Set: See OEM documentation.
(See OEM documentation.)
OEM and are implemented in the
Clear: See OEM documentation.
application-specific VCL code. See
OEM documentation.
68 VCL Run Time Error 1. VCL code encountered a runtime Set: Runtime VCL code error condition.
VCL error. Clear: Edit VCL application software to
2. See Monitor menu » Controller: fix this error condition; flash the new
VCL Error Module and VCL Error. compiled software and matching
This error can then be compared to parameter defaults; cycle KSI.
the runtime VCL module ID and
error code definitions found in the
specific OS system information file.
69 External Supply Out of Range 1. External load on the 5V and 12V Set: The external supply current (combined
None, unless a fault action
supplies draws either too much or current used by the 5V supply [pin 26]
is programmed in VCL. too little current. and 12V supply [pin 25]) is either greater
2. Fault Checking Menu parameters than the upper current threshold or lower
Ext Supply Max and Ext Supply Min than the lower current threshold. The two
are mis-tuned. thresholds are defined by the External
3. See Monitor menu » Outputs: Supply Max and External Supply Min
Ext Supply Current. parameter settings (page 47).
Clear: Bring the external supply current
within range.
71 OS General 1. Internal controller fault. Set: Internal controller fault detected.
Clear: Cycle KSI.
ShutdownMotor;
ShutdownMainContactor;
ShutdownEMBrake;
ShutdownThrottle;
ShutdownInterlock;
ShutdownDriver1;
ShutdownDriver2;
ShutdownDriver3;
ShutdownDriver4;
ShutdownPD;
FullBrake;
ShutdownPump.
ShutdownMotor;
ShutdownMainContactor;
ShutdownEMBrake;
ShutdownThrottle;
ShutdownInterlock;
ShutdownDriver1;
ShutdownDriver2;
ShutdownDriver3;
ShutdownDriver4;
ShutdownPD;
FullBrake;
ShutdownPump.