D-EIMHP01702-23_00EN- 41/72
7.1.3 Reference drawing in case of custom water piping
In case the manifold module is not provided by Daikin, it is possible to refer to the following indication for customer piping connection.
Fig. 25 – Water piping configuration
When pump module is not equipped, the customer can connect the plant water piping indifferently to the left or right side of the
manifold modules system. When pump module is supplied, the water connection can only be done to the pump suction pipe.
Connection of modular system
7.2.1 Mechanical connection
The mechanical connection of more modular systems together is possible thanks to a positioning kit.
The positioning kit allows to align perfectly the two systems for a proper connection.
Fig. 26 – Modular systems connection