D-EIMHP01702-23_00EN- 24/72
Fig. 11 – Reference drawing for evaporator and condenser identification
1
Condenser
2
Evaporator
3
Electrical panel
The units have a water input and output for the connection of the chiller to water circuit of the system. This circuit must be
connected to the unit by an authorised technician and must comply with all the current national and local regulations on the subject.
If dirt penetrates the water circuit, there could be problems. Therefore always remember the following when
connecting the water circuit:
1.only use pipes that are clean inside.
2.keep the end of the pipe facing downward when removing the burrs.
3.cover the end of the pipe when inserting it through a wall to avoid dust and dirt getting in.
4.clean the pipes of the system located between the filter and the unit, with running water, before connecting
it to the system.
1
2
3