EasyManua.ls Logo

Daikin EWWT100Q - Table 7 - Standard Routine Maintenance Plan

Daikin EWWT100Q
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D-EIMHP01702-23_00EN- 65/72
Table 7 - Standard Routine Maintenance Plan
Routine maintenance programme (Note 2)
Weekly
Monthly
(Note 1)
Yearly
(Note 2)
General
Reading of operating data (Note 3)
X
Visual inspection of machine for any damage and/or loosening
X
Verification of thermal insulation integrity
X
Clean and paint where necessary
X
Analysis of water (Note 5)
X
Electrical:
Verification of control sequence
X
Verify contactor wear Replace if necessary
X
Verify that all electrical terminals are tight Tighten if necessary
X
Clean inside the electrical control board
X
Visual inspection of components for any signs of overheating
X
Verify operation of compressor and electrical resistance
X
Measure compressor motor insulation using the Megger
X
Refrigeration circuit:
Check for any refrigerant leakage
X
Verify filter dryer pressure drop
X
Verify oil filter pressure drop (Note 4)
X
Analyse compressor vibrations
X
Analyse compressor oil acidity (Note 6)
X
Check safety valves (Note 7)
X
Condenser section:
Clean the exchangers (Note 8)
X
General
Reading of operating data (Note 3)
X
Notes:
1. Monthly activities include all the weekly ones.
2. The annual (or early season) activities include all weekly and monthly activities.
3. Daily reading of the operating values of the unit allows maintaining high observational standards.
4. Check for any dissolved metals.
5. Check that the cap and the seal have not been tampered with. Check that the drainage connection of the safety valves is not accidentally
occluded by foreign objects, rust or ice. Check the manufacturing date on the safety valve and replace it, if necessary, in compliance with the
national laws in force.
6. Clean water heat exchangers with appropriate chemicals. Particles and fibers could clog up the exchangers, especially for water exchangers
pay attention if water rich in calcium carbonate is used. An increase in pressure drops or a decrease in thermal efficiency means that the heat
exchangers are clogged. In environments with a high concentration of air-borne particles, it might be necessary to clean the condenser bank
more often.
7. TAN (Total acid number): 0.10: No action
Between 0.10 and 0.19: Replace anti-acid filters and re-check after 1000 running hours. Continue to replace the filters
until the TAN is below 0.10.
0.19: replace oil, oil filter and oil filter dryer. Verify at regular intervals.

Table of Contents

Related product manuals