Appendix SiE33-102
106 General Information
7.4.3 PIPE SIZE REDUCER (For R-22)
This kit including followings;
This kits are pipe size reducers for REFNET JOINT and HEADER and applicable to following
REFNET CONNECTOR.
1. Select the field piping size according to the installation manual of the BRANCH PIPING KIT.
2. Connect the PIPE SIZE REDUCER suitable for the field piping size to the branch piping kit.
ex.)Connect the reducers to the branch piping kit, KHRJ26K75T. For inlet piping size is φ41.3 and outlet
1·2 piping size are φ34.9.
Name Pipe size reducer (1) Pipe size reducer (2) Pipe size reducer (3)
Figure
Q’ty
KHRJ26K40TP 1 — 1
KHRJ26K40HP — — 1
KHRJ26K75TP 1 1 1
Kit Name REFNET CONNECTOR
KHRJ26K40TP KHRJ26K40T (Gas pipe)
KHRJ26K40HP KHRJ26K40H (Gas pipe)
KHRJ26K75TP KHRJ26K75T (Gas pipe)
(V1071)
(V1072)
(V1073)
The figure and size of pipe size reducers are as followings;
Pipe size reducer (1) Pipe size reducer (2) Pipe size reducer (3)
For φ34.9, cut the center of the part A.
ID φ34.9
OD φ31.8
124
(V1074)
Field
piping side
( )
124
ID φ41.3
OD φ38.1
Field
piping side
( )
(V1075)
185
ID φ41.3
ID φ34.9
OD φ31.8
Field
piping side
( )
(V1076)
Port A
Dimple
PIPE SIZE REDUCER (2) PIPE SIZE REDUCER (3)
PIPE SIZE REDUCER (1)
CONNECTIONS
CONNECTIONS
CONNECTIONS
CUT AT THE CENTER
OF THE CONNECTIONS
WITH A PIPE CUTTER
CUT AT THE CENTER
OF THE CONNECTIONS
WITH A PIPE CUTTER
CUT AT THE CENTER
OF THE CONNECTIONS
WITH A PIPE CUTTER
ID φ44.5
KHRJ26K75T
(GAS SIDE)
ID φ38.1
ID φ38.1
ID φ38.1
ID φ25.4
ID φ31.8
OUTLET 1
OUTLET 2
FIELD PIPING
φ
41.3
INLET
FIELD PIPNG
φ
34.9
(V1829)
Si33-102.book Page 106 Tuesday, June 26, 2001 3:18 PM