8.7.5.2 Uploading Parameters to Control Panel (Up To Keypad, S6.3.2)
Context:
Use this function to upload all parameter groups to the control panel when the AC drive is stopped.
Procedure
1. In the Copy parameters (S6.3) subpage, find the Up to keypad page (S6.3.2).
2. Push the Menu button Right.
3. To go to the edit mode, push the Menu button Right.
All param. starts to blink.
4. To accept the selection, push the [enter] button.
5. Wait until OK shows on the display.
8.7.5.3 Downloading Parameters to Drive (Down From Keypad, S6.3.3)
Context:
Use this function to download 1 or all parameter groups from the control panel to an AC drive when the AC drive is stopped.
Procedure
1. In the Copy parameters (S6.3) subpage, find the Down from keypad page (S6.3.3).
2. Push the Menu button Right.
3. To go to the edit mode, push the Menu button Right.
4. Use the Browser buttons to select 1 of these 3 options:
All parameters (All param.)
All parameters but the motor nominal value parameters (All. no motor)
Application parameters
5. To accept the selection, push the [enter] button.
6. Wait until OK shows on the display.
8.7.5.4 Activating or Deactivating the Automatic Parameter Back-up (P6.3.4)
Context:
Use these instructions to activate or deactivate the parameter back-up.
Prerequisites:
When the application is changed, the parameters in the parameter settings on page S6.3.1 are deleted. To copy parameters from one
application to a different application, first upload them to the control panel.
Using the Control Panel
Operating guide | VACON® NXS/NXP Air-cooled
DPD00910G
102 | Danfoss A/S © 2018.06

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Vacon NXP Series and is the answer not in the manual?

Danfoss Vacon NXP Series Specifications

General IconGeneral
BrandDanfoss
ModelVacon NXP Series
CategoryController
LanguageEnglish

Related product manuals