12.7.7 Power Ratings for Mains Voltage 525–690 V (UL Rating 600 V), North America
Table 50: Power Ratings in Mains 525–600 V, 60 Hz, 3~
Enclosure
size
Drive
type
Input
current
I
in
(1)
Low
loadabili-
ty: I
L
[A]
(2)
Low
loadabili-
ty: 10%
overload
I [A]
High
loadabili-
ty: I
H
[A]
(2)
High
loadabili-
ty: 50%
overload
I [A]
Loadabili-
ty: Max I
S
2 s
Motor
shaft
power
(3)
:
10% over-
load
104°F [hp]
Motor
shaft
power
(3)
:
50% over-
load
122°F [hp]
FR6 0004 4.5 4.5 5.0 3.2 4.8 6.4 3 2
0005 5.5 5.5 6.1 4.5 6.8 9.0 4 3
0007 7.5 7.5 8.3 5.5 8.3 11.0 5 4
0010 10.0 10.0 11.0 7.5 11.3 15.0 7.5 5
0013 13.5 13.5 14.9 10.0 15.0 20.0 10 7.5
0018 18.0 18 19.8 13.5 20.3 27.0 15 10
0022 22.0 22.0 24.2 18.0 27.0 36.0 20 15
0027 27.0 27.0 29.7 22.0 33.0 44.0 25 20
0034 34.0 34.0 37.0 27.0 41.0 54.0 30 25
FR7 0041 41.0 41.0 45.0 34.0 51.0 68.0 40 30
0052 52.0 52.0 57.0 41.0 62.0 82.0 50 40
FR8 0062 62.0 62.0 68.0 52.0 78.0 104.0 60 50
0080 80.0 80.0 88.0 62.0 93.0 124.0 75 60
0100 100.0 100.0 110.0 80.0 120.0 160.0 100 75
FR9 0125 125.0 125.0 138.0 100.0 150.0 200.0 125 100
0144 144.0 144.0 158.0 125.0 188.0 250.0 150 125
0170 170.0 170.0 187.0 144.0 216.0 288.0 150 150
0208 208.0 208.0 229.0 170.0 255.0 340.0 200 150
FR10
(3)
0261 261.0 261.0 287.0 208.0 312.0 416.0 250 200
0325 325.0 325.0 358.0 261.0 392.0 522.0 350 250
0385 385.0 385.0 424.0 325.0 488.0 650.0 400 350
0416 416.0 416.0 358.0 325.0 488.0 650.0 450 350
FR11
(3)
0460 460.0 460.0 506.0 385.0 578.0 770.0 500 450
0502 502.0 502.0 552.0 460.0 690.0 920.0 550 500
0590 590.0 590.0 649.0 502.0 753.0 1004.0 600 550
1
The currents in given ambient temperatures are achieved only when the switching frequency is the same or smaller than the factory default.
2
See 12.7.1 Overload Capability
3
575 V
Specifications
Operating guide | VACON® NXS/NXP Air-cooled
DPD00910G | 153
Danfoss A/S © 2018.06