Enclosure
size
Drive type I
L
[A] Fuse
(gG/gL) [A]
Mains, motor and
brake resistor cable Cu
(1)
[mm
2
]
Mains terminal [mm
2
]
Grounding terminal
[mm
2
]
FR7 0075 2
0072 5
75
72
80 3*25+16 2.5–50 Cu
6–50 Al
6–70
0088 2
0087 5
88
87
100 3*35+16 2.5–50 Cu
6–50 Al
6–70
0114 2
0105 5
114
105
125 3*50+25 2.5–50 Cu
6–50 Al
6–70
FR8 0140 2
0140 5
140 160 3*70+35 25–95 Cu/Al 6–95
0170 2
0168 5
168 200 3*95+50 95–185 Cu/Al 6–95
0205 2
0205 5
205 250 3*150+70 95–185 Cu/Al 6–95
FR9 0261 2
0261 5
261 315 3*185+95 or
2*(3*120+70)
95–185 Cu/Al 6–95
0300 2
0300 5
300 315 2*(3*120+70) 95–185 Cu/Al 6–95
1
Uses a correction factor 0.7
12.3.3 Cable and Fuse Sizes for 208–240 V and 380–500 V, FR4 to FR9, North America
Table 35: Cable and Fuse Sizes for VACON
®
NXS/NXP, North America
Enclo-
sure size
Drive type Fuse Class
Fast Act-
ing (T/J)
[A]
Mains, Motor, and brake re-
sistor cable Cu [AWG]
(1) (2)
Mains terminal [AWG] Grounding terminal
[AWG]
FR4 0003 2—0008 2
0003 5—0007 5
10 3*16 AWG + 16 AWG 18 AWG - 4 AWG 18 AWG - 4 AWG
0009 5 15 3*16 AWG + 16 AWG 18 AWG - 4 AWG 18 AWG - 4 AWG
0011 2—0012 2
0012 5
15 3*14 AWG + 14 AWG 18 AWG - 4 AWG 18 AWG - 4 AWG
Specifications
Operating guide | VACON® NXS/NXP Air-cooled
DPD00910G
138 | Danfoss A/S © 2018.06