Procedure
1. To find the Active faults menu, scroll down in the main menu until the location indication M4 shows on the first line of the display.
READY
I/O term
F0
e30bg035.10
Active faults
2. To go to the Active faults menu from the main menu, push the Menu button Right.
If there is a fault in the display, these symbols show:
T1 T13
F
STOP
I/O term
FAULT
B
A
e30bg036.10
11 Output phase
A Fault symbol B Fault type symbol
Illustration 41: Fault Symbols
8.5.2 Examining the Fault Time Data Record
Context:
This menu shows some important data that was valid at the time of the fault. This helps to find the cause of the fault.
Procedure
1. Find the fault in Active faults menu or Fault history menu.
2. Push the Menu button Right.
3. Scroll the data T.1-T.16 with the Browser buttons.
8.5.3 Fault Time Data Record
The fault time data record shows some important data that was valid at the time of the fault. This helps to find the cause of the fault.
If real time is set on the AC drive, the data items T1 and T2 show as in column Real Time Data Record.