12.3 Cable and Fuse Sizes
12.3.1 List of Cable and Fuse Size Information
This topic lists the links to find the cable and fuse size tables for VACON™ NXS and NXP Air Cooled AC Drive.
12.3.2 Cable and Fuse Sizes for 208–240 V and 380–500 V, FR4 to FR9
12.3.4 Cable and Fuse Sizes for 525–690 V, FR6 to FR9
12.3.6 Cable and Fuse Sizes for 380–500 V, FR10 to FR11
12.3.8 Cable and Fuse Sizes for 525–690 V, FR10 to FR11
For AC Drives in North America, see:
12.3.3 Cable and Fuse Sizes for 208–240 V and 380–500 V, FR4 to FR9, North America
12.3.5 Cable and Fuse Sizes for 525–690 V (UL Rating 600 V), FR6 to FR9, North America
12.3.7 Cable and Fuse Sizes for 380–500 V, FR10 to FR11, North America
12.3.9 Cable and Fuse Sizes for 525–690 V (UL Rating 600 V), FR10 to FR11, North America
12.3.2 Cable and Fuse Sizes for 208–240 V and 380–500 V, FR4 to FR9
Table 34: Cable and Fuse Sizes for VACON
®
NXS/NXP
Enclosure
size
Drive type I
L
[A] Fuse
(gG/gL) [A]
Mains, motor and
brake resistor cable Cu
(1)
[mm
2
]
Mains terminal [mm
2
]
Grounding terminal
[mm
2
]
FR4 0003 2—0008 2
0003 5—0009 5
3–8
3–9
10 3*1.5+1.5 1–4 1–4
0011 2—0012 2
0012 5
11–12
12
16 3*2.5+2.5 1–4 1–4
FR5 0017 2
0016 5
17
16
20 3*4+4 1–10 1–10
0025 2
0022 5
25
22
25 3*6+6 1–10 1–10
0031 2
0031 5
31
31
35 3*10+10 1–10 1–10
FR6 0048 2
0038 5—0045 5
48
38–45
50 3*10+10 2.5–50 Cu
6–50 Al
2.5–35
0061 2
0061 5
61 63 3*16+16 2.5–50 Cu
6–50 Al
2.5–35
Specifications
Operating guide | VACON® NXS/NXP Air-cooled
DPD00910G | 137
Danfoss A/S © 2018.06