12.3.5 Cable and Fuse Sizes for 525–690 V (UL Rating 600 V), FR6 to FR9, North America
Table 37: Cable and Fuse Sizes for VACON
®
NXS/NXP, North America, UL Rating 525–600 V
Enclo-
sure size
Drive type Fuse Class
Fast Acting
(T/J) [A]
Mains, Motor, and brake re-
sistor cable Cu [AWG]
(1) (2)
Mains terminal [AWG] Grounding terminal
[AWG]
FR6 0004 6—0007 6 10 3*14 AWG + 14 AWG 14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
0010 6 15 3*14 AWG + 14 AWG 14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
0013 6 20 3*14 AWG + 14 AWG 14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
0018 6 25 3*12 AWG + 12 AWG 14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
0022 6 30 3*10 AWG + 10 AWG 14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
0027 6 40 3*8 AWG + 8 AWG 14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
0034 6 50 3*8 AWG + 8 AWG 14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
14 AWG - 2 AWG
FR7 0041 6 50 3*8 AWG + 8 AWG 14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
10 AWG - 1 AWG
0052 6 70 3*6 AWG + 6 AWG 14 AWG - 1 AWG Cu
10 AWG - 1 AWG Al
10 AWG - 1 AWG
FR8 0062 6 80 3*4 AWG + 6 AWG 4 AWG - 3/0 AWG Cu/Al 10 AWG - 3/0 AWG
0080 6 100 3*4 AWG + 6 AWG 4 AWG - 3/0 AWG Cu/Al 10 AWG - 3/0 AWG
0100 6 125 3*2 AWG + 6 AWG 4 AWG - 3/0 AWG Cu/Al 10 AWG - 3/0 AWG
FR9 0125 6—0144 6 200 3*3/0 AWG + 1/0 AWG 3/0 AWG - 350 kcmil Cu/Al 10 AWG - 3/0 AWG
0170 6 250 3*3/0 AWG + 1/0 AWG 3/0 AWG - 350 kcmil Cu/Al 10 AWG - 3/0 AWG
0208 6 300 3*300 kcmil + 2/0 AWG 3/0 AWG - 350 kcmil Cu/Al 10 AWG - 3/0 AWG
1
Uses a correction factor 0.7.
2
Use cables with a +90 °C (194 °F) heat resistance to comply with the UL standards.
Specifications
Operating guide | VACON® NXS/NXP Air-cooled
DPD00910G | 141