12.8 VACON NXP Technical Data
Table 51: Technical Data
Technical item or function Technical data
Connection of mains Input voltage U
in
208–240 V, 380–500 V, 525–690 V, UL rating up to 600 V, -10%…+10%
Input frequency 45–66 Hz
Connection to mains Once per minute or less
Starting delay 2 s (FR4 to FR8), 5 s (FR9)
Network imbalance Max. ±3% of the nominal voltage
Mains Mains types: TN, TT, and IT short-circuit current: the maximum short-cir-
cuit current must be < 100 kA.
Motor connection Output voltage 0-Uin
Constant output current I
L
: Ambient temperature max. +40 °C (104 °F) overload 1.1 x I
L
(1 min/
10 min)
I
H
: Ambient temperature max. +50 °C (122 °F) overload 1.5 x I
H
(1 min/
10 min)
For 50–55 °C ambient temperatures use derating factor I
H
*2.5% / °C
Starting current IS for 2 s each 20 s. After 2 s the current controller makes it go down to
150% I
H
.
Output frequency 0–320 Hz (standard NXP and NXS); 7200 Hz (special NXP with special
software)
Frequency resolution 0.01 Hz (NXS); Application-dependent (NXP)
Specifications
Operating guide | VACON® NXS/NXP Air-cooled
DPD00910G
154 | Danfoss A/S © 2018.06

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Vacon NXP Series and is the answer not in the manual?

Danfoss Vacon NXP Series Specifications

General IconGeneral
BrandDanfoss
ModelVacon NXP Series
CategoryController
LanguageEnglish

Related product manuals