12.7.5 Power Ratings for Mains Voltage 380–500 V, North America
Table 48: Power Ratings in Mains 380–500 V, 60 Hz, 3~
Enclosure
size
Drive
type
Input
current
I
in
(1)
Low load-
ability: I
L
[A]
(2)
Low load-
ability:
10%
overload
I [A]
High
loadabili-
ty: I
H
[A]
(2)
High
loadabili-
ty: 50%
overload
I [A]
Loadabili-
ty: Max I
S
2 s
Motor
shaft pow-
er
(3)
: 10%
overload
104°F [hp]
Motor
shaft pow-
er
(3)
: 50%
overload
122°F [hp]
FR4 0003 3.3 3.3 3.6 2.2 3.3 4.4 2 1.5
0004 4.3 4.3 4.7 3.3 5 6.6 3 2
0005 5.6 5.6 6.2 4.3 6.5 8.6 4 3
0007 7.6 7.6 8.4 5.6 8.4 11.2 5 4
0009 9 9 9.9 7.6 11.4 15.2 7.5 5
0012 12 12 13.2 9 13.5 18 10 7.5
FR5 0016 16 16 17.6 12 18 24 13 10
0022 23 23 25.3 16 24 32 20 13
0031 31 31 34 23 35 44 25 20
FR6 0038 38 38 42 31 47 62 30 25
0045 46 46 49.5 38 57 76 40 30
0061 61 61 67 46 69 92 50 40
FR7 0072 72 72 79 61 92 122 60 50
0087 87 87 96 72 108 144 75 60
0105 105 105 116 87 131 174 90 75
FR8 0140 140 140 154 105 158 210 125 90
0168 170 170 187 140 210 280 150 125
0205 205 205 226 170 255 340 175 150
FR9 0261 261 261 287.1 205 308 410 200 175
0300 300 300 330 245 368 490 250 200
FR10
(3)
0385 385 385 424 300 450 600 350 250
0460 460 460 506 385 578 770 400 350
0520 520 520 576 460 690 920 450 400
FR11
(3)
0590 590 590 649 520 780 1040 500 450
0650 650 650 715 590 885 1180 600 500
0730 730 730 803 650 975 1300 650 600
1
The currents in given ambient temperatures are achieved only when the switching frequency is the same or smaller than the factory default.
2
See 12.7.1 Overload Capability
3
480 V
Specifications
Operating guide | VACON® NXS/NXP Air-cooled
DPD00910G | 151
Danfoss A/S © 2018.06