EasyManua.ls Logo

Danfoss Vacon NXP Series - Cable and Fuse Sizes for 525-690 V, FR10 to FR11

Danfoss Vacon NXP Series
174 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Enclo-
sure size
Drive type Fuse Class Fast
Acting (T/J) [A]
Mains, Motor, and brake resistor cable Cu [AWG]
(1)
(2)
Number of
supply ca-
bles
Number of
motor cables
FR11 0590 5 400 (6 pcs) Cu: 2*(3*500 kcmil + 250 kcmil)
Al: 4*(3*250 kcmil Al + 1 AWG Cu)
Even Even/Odd
0650 5 400 (6 pcs) Cu: 4*(3*3/0 AWG + 1/0 AWG)
Al: 4*(3*300 kcmil Al + 1 AWG Cu)
Even Even/Odd
0730 5 500 (6 pcs) Cu: 4*(3*300 kcmil + 2/0 AWG)
Al: 4*(3*350 kcmil Al + 1/0 AWG Cu)
Even Even/Odd
1
Uses a correction factor 0.7.
2
Use cables with a +90 °C (194 °F) heat resistance to comply with the UL standards.
12.3.8 Cable and Fuse Sizes for 525–690 V, FR10 to FR11
Table 40: Cable and Fuse Sizes for VACON
®
NXS/NXP
Enclo-
sure size
Drive type I
L
[A] Fuse (gG/gL)
[A]
Mains, motor, and brake resistor cable
(1)
[mm
2
]
Number of
supply cables
Number of
motor cables
FR10 0261 6 261 315 (3 pcs) Cu: 3*185+95
Al: 2*(3*95Al+29Cu)
Even/Odd Even/Odd
0325 6 325 400 (3 pcs) Cu: 2x(3*95 + 50)
Al: 2*(3*150Al+41Cu)
Even/Odd Even/Odd
0385 6 385 400 (3 pcs) Cu: 2*(3*120+70)
Al: 2*(3*185Al+57Cu)
Even/Odd Even/Odd
0416 6 416 500 (3 pcs) Cu: 2*(3*150+70)
Al: 2*(3*185Al+57Cu)
Even/Odd Even/Odd
FR11 0460 6 460 500 (3 pcs) Cu: 2*(3*150+70)
Al: 2*(3*240Al+72Cu)
Even/Odd Even/Odd
0502 6 502 630 (3 pcs) Cu: 2*(3*185+95)
Al: 2*(3*300Al+88 Cu)
Even/Odd Even/Odd
0590 6 590 315 (6 pcs) Cu: 2*(3*240+120)
Al: 4*(3*120Al+41Cu)
Even Even/Odd
1
Uses a correction factor 0.7
Specifications
Operating guide | VACON® NXS/NXP Air-cooled
DPD00910G | 143
Danfoss A/S © 2018.06