Index Monitored value Unit ID Description
V1.1 Output frequency Hz 1 The output frequency to the motor
V1.2 Frequency reference Hz 25 The frequency reference to motor control
V1.3 Motor speed rpm 2 The actual speed of the motor in rpm
V1.4 Motor current A 3 Measured motor current
V1.5 Motor torque % 4 The calculated shaft torque
V1.6 Motor power % 5 The calculated motor shaft power in percentage
V1.7 Motor voltage V 6 The output voltage to the motor
V1.8 DC link voltage V 7 The measured voltage in the DC-link of the drive
V1.9 Unit temperature °C 8 The heat sink temperature in Celsius or Fahrenheit
V1.10 Motor temperature % 9 The calculated motor temperature in percentage of the nominal temperature. See
VACON
®
All in One Application Manual.
V1.11 Analog input 1 V/mA 13
AI1
(1)
V1.12 Analog input 2 V/mA 14
AI2
(1)
V1.13 DIN 1, 2, 3 15 Shows the status of the digital inputs 1-3
V1.14 DIN 4, 5, 6 16 Shows the status of the digital inputs 4-6
V1.15 DO1, RO1, RO2 17 Shows the status of the digital and relay outputs 1-3
V1.16 Analog I
out
mA 26 AO1
V1.17 Multimonitoring items Shows 3 monitored values to select from. See
8.7.6.9 Enabling/Disabling the Change
of Multimonitoring Items.
1
If the AC drive only has +24 V supply (for control board power-up), this value is not reliable.
See VACON
®
All in One Application Manual for more monitored values.
8.3 Using the Parameter Menu (M2)
8.3.1 Finding the Parameter
Context:
Use these instructions to find the parameter to edit.
Using the Control Panel
Operating guide | VACON® NXS/NXP Air-cooled
DPD00910G | 87
Danfoss A/S © 2018.06