B1
D1
A1
B2 A2
C1
D2
C2
e30bg081.10
MAINS
MOTOR
Grounding conductor
Illustration 55: Cable Stripping
Table 42: Cable Stripping Lengths [mm]
Enclosure size A1 B1 C1 D1 A2 B2 C2 D2
FR4 15 35 10 20 7 50 7 35
FR5 20 40 10 30 20 60 10 40
FR6 20 90 15 60 20 90 15 60
FR7 25 120 25 120 25 120 25 120
FR8
0140
0168—0205
23
28
240
240
23
28
240
240
23
28
240
240
23
28
240
240
FR9 28 295 28 295 28 295 28 295
Table 43: Cable Stripping Lengths [in]
Enclosure size A1 B1 C1 D1 A2 B2 C2 D2
FR4 0.59 1.38 0.39 0.79 0.28 1.97 0.28 1.38
FR5 0.79 1.57 0.39 1.18 0.79 2.36 0.79 1.57
FR6 0.79 3.54 0.59 2.36 0.79 3.54 0.59 2.36
FR7 0.98 4.72 0.98 4.72 0.98 4.72 0.98 4.72
FR8
0140
0168—0205
0.91
1.10
0.91
1.10
0.91
1.10
0.91
1.10
0.91
1.10
0.91
1.10
0.91
1.10
0.91
1.10
FR9 1.10 11.61 1.10 11.61 1.10 11.61 1.10 11.61