Technical item or function Technical data
Ambient conditions Shock
IEC/EN 60068-2-27
UPS Drop Test (for applicable UPS weights) Storage and shipping: max.
15 G, 11 ms (in package)
Protection rating IP21 (UL Type 1) standard in entire kW/HP range
IP54 (UL Type 12) option in FR4 to FR10. For IP54 (UL Type 12), a keypad
is necessary.
Pollution degree PD2
EMC (at default set-
tings)
Immunity Low frequency:
Complies with IEC 61000-3-12, when R
SCE
>120 and In < 75 A
High frequency:
Complies with IEC/EN 61800-3 + A1, 1st and 2
nd
environment
Emissions Depend on EMC level. See
table 2.
Noise level Average noise level (cooling
fan) in dB(A)
The sound pressure depends on the cooling fan speed, which is control-
led in accordance with the drive temperature.
FR4: 44
FR5: 49
FR6-FR7: 57
FR8: 58
FR9-FR11: 76
Safety standards IEC/EN 61800-5-1, UL 508C, CSA C22.2 No.274
Approvals CE, cULus, RCM, KC, EAC, UA. (See the nameplate of the drive for more
approvals.) Marine approvals: LR, BV, DNVGL, ABS, RMRS, CCS, KR.
Efficiency See http://drives.danfoss.com/knowledge-center/energy-efficiency-di-
rective/#/
Specifications
Operating guide | VACON® NXS/NXP Air-cooled
DPD00910G | 157