Fault
code
Fault Subcode
in T.14
Possible cause How to correct the fault
11
(1)
Output phase
supervision
The measurement of current tells that
there is no current in 1 motor phase.
Do a check of the motor cable and the motor.
12 Brake chopper
supervision
There is no brake resistor. The brake re-
sistor is broken. A defective brake
chopper.
Do a check of the brake resistor and the ca-
bling.
If they are in good condition, there is a fault
in the resistor or the brake chopper. Ask in-
structions from the local distributor.
13 Frequency
converter un-
dertempera-
ture
Too low a temperature in the heat sink
of the power unit or in the power
board. The heat sink temperature is be-
low -10 °C (14 °F).
14 Frequency
converter
overtempera-
ture
heat sink temperature is over 90 °C
(194 °F) (or 77 ºC (170.6 °F), NX_6, FR6).
Overtemperature alarm is issued when
the heat sink temperature goes over
85 °C (185 °F) (72 ºC (161.6 °F)).
Do a check of the actual amount and flow of
cooling air.
Examine the heat sink for dust.
Do a check of the ambient temperature.
Make sure that the switching frequency is
not too high in relation to the ambient tem-
perature and the motor load.
15
(1)
Motor stalled The motor stalled. Do a check of the motor and the load.
16
(1)
Motor over-
temperature
There is too heavy a load on the motor. Decrease the motor load. If there is no motor
overload, do a check of the temperature
model parameters.
17
(1)
Motor under-
load
Motor underload protection has trip-
ped.
Do a check of the load.
18
(2)
Unbalance S1 = Cur-
rent unbal-
ance
Unbalance between power modules in
paralleled power units.
If the fault occurs again, ask instructions from
the local distributor.
S2 = DC
voltage
unbalance
22 EEPROM
checksum fault
Parameter save fault.
operation malfunction
defective component
If the fault occurs again, ask instructions from
the local distributor.
24
(2)
Counter fault Values that showed on the counters
are incorrect
25 Microproces-
sor watchdog
fault
operation malfunction
defective component
Reset the fault and start the drive again.
If the fault shows again, ask instructions from
the local distributor.