N O T I C E
Disabling of the auto-crossover function requires crossed Ethernet cables for daisy-chaining the options.
Option
Name
Description
[0]
Disabled
[1]*
Enabled
Parameter 12-92 IGMP Snooping
Table 662: Parameter 12-92 IGMP Snooping
12-92 IGMP Snooping
Default value: [1] Enabled
Parameter type: Option
Setup: 2 setups
Conversion index: –
Data type: Uint8
Change during operation: True
This function presents flooding of the Ethernet protocol stack by only forwarding multicast packets to ports that are a member of
the multicast group.
Option
Name
Description
[0]
Disabled
[1]*
Enabled
Parameter 12-93 Cable Error Length
Table 663: Parameter 12-93 Cable Error Length
12-93 Cable Error Length
Default value: 0
Parameter type: Range, 0 - 65535
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: True
If cable diagnostics is enabled in parameter 12-90 Cable Diagnostic, the built-in switch is possible via time domain reflectometry
(TDR). This is a measurement technique which detects common cabling problems such as open circuits, short circuits, and impe-
dance mismatches or breaks in transmission cables. The distance from the option to the error is shown in meters with an accuracy of
±2 m (6.6 ft). The value 0 means no errors detected.
Parameter 12-94 Broadcast Storm Protection
Table 664: Parameter 12-94 Broadcast Storm Protection
12-94 Broadcast Storm Protection
Default value: -1
Parameter type: Range, -1 - 20%
Setup: 2 setups
Conversion index: 0
Data type: Int8
Change during operation: True
The built-in switch is capable of protecting the switch system from receiving too many broadcast packages, which can use up net-
work resources. The value indicates a percentage of the total bandwidth that is allowed for broadcast messages. Example: OFF
means that the filter is disabled - all broadcast messages are passed through. The value 0% means that no broadcast messages are
passed through. A value of 10% means that 10% of the total bandwidth is allowed for broadcast messages. If the amount of broad-
cast messages exceeds the 10% threshold, they are blocked.
AU275636650261en-000101 / 130R0334370 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals