EasyManuals Logo
Home>Danfoss>DC Drives>VLT AutomationDrive FC 302

Danfoss VLT AutomationDrive FC 302 Programming Guide

Danfoss VLT AutomationDrive FC 302
722 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #364 background imageLoading...
Page #364 background image
Parameter 12-41 Slave Message Count
Table 639: Parameter 12-41 Slave Message Count
12-41 Slave Message Count
Default value: 0
Parameter type: Range, 0 - 0
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: True
This parameter is read-only. It shows the number of Modbus messages received and processed by the follower drive.
Parameter 12-42 Slave Exception Message Count
Table 640: Parameter 12-42 Slave Exception Message Count
12-42 Slave Exception Message Count
Default value: 0
Parameter type: Range, 0 - 0
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: True
This parameter is read-only. It shows the number of Modbus messages for which the follower has sent an exception response.
5.12.6 12-4* Fieldbus Extension
Parameter 12-49 Ethernet Extended Status
Table 641: Parameter 12-49 Ethernet Extended Status
12-49 Ethernet Extended Status
Default value: 0
Parameter type: Range, 0 - 0xFFFFFFFF
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: True
5.12.7 12-5* EtherCAT
Parameter 12-50 Configured Station Alias
Table 642: Parameter 12-50 Configured Station Alias
12-50 Configured Station Alias
Default value: 0
Parameter type: Range, 0 - 65535
Setup: 1 setup
Conversion index: 0
Data type: Uint16
Change during operation: False
Changes are first active after a power cycle. If the DIP switches are all set to ON or all to OFF, the display setting has priority over the
DIP switch. Otherwise, the DIP switch settings have priority over the parameter. In this case, the parameter reflects the setting of the
DIP switches. Changes to the DIP switch setting are active after a power-up.
Parameter 12-51 Configured Station Address
Table 643: Parameter 12-51 Configured Station Address
12-51 Configured Station Address
Default value: 0
Parameter type: Range, 0 - 65535
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: True
This parameter shows the configured station address. The parameter can only be set by the master at power-up.
AU275636650261en-000101 / 130R0334364 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals